Measurement and Test Automation
deutsch

Signal Aquisition:
The Measurement and I/O Level

Q.bloxx Modules

 Input Types ↓A101A102A103A104A106A107A108A109A123A124A128D101D104D105
Voltage        
Voltage
(1,2 kV isolation)
             
Voltage
(range up to 1,2 kV)
             
Current         
Resistance            
Potentiometer            
Pt100, Pt1000            
Thermocouple           
Thermocouple
(1,2 kV isolation)
             
Full Half and Quarter Bridges          
Inductive Full and Half Bridges             
LVDT             
IEPE/ICP Sensors            
Frequency Signal            
Pulse Width             
Counter            
Time            
Status       
 Output Signal ↓A101A102A103A104A106A107A108A109A123A124A128D101D104D105
Voltage           
Current           
Frequency Signal            
Pulse Width            
Status       
 Number of channels21882484444/281616
 Data Rates (Hz)100 k100 k10010010 k10 k10 k100 k10 k10 k100 k10 k100 k100 k
 Details ↓A101A102A103A104A106A107A108A109A123A124A128D101D104D105

Hint: In case you can not see the complete table use the F11 key to switch to full screen mode.

 

Q.bloxx Module A101

  • 2 universal analog input channels
  • voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges, IEPE-sensors
  • Fast high accuracy digitalization
  • 24 bit ADU, 100 kHz sample rate per channel
  • 1 digital in or output per channel
  • input: state, tare, memory reset
    output: state alarm, thresh hold
  • Signal conditioning
  • 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • TEDS
  • class 1 and class 2, according IEEE 1541.4
  • RS485 fieldbus interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module A102

  • 1 analog input channel
  • measuring bridge (full, half, quarter), IEPE-sensors, voltage, current
  • 1 analog output
  • voltage ±10 V and current 0 up to 25 mA selectable, 100 kHz
  • Fast high accuracy digitalization
  • 19 Bit ADC - SAR (without delay time), 100 kHz sample rate
  • 4 digital inputs, 2 digital outputse
  • input: state, tare, memory reset
    output: state alarm, thresh hold
  • Signal conditioning
  • 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • TEDS
  • class 1 and class 2, according IEEE 1541.4
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Additional RS 485 fieldbus interface
  • to control an 8-channel multiplexer for multi channel systems, 10 Hz per channel
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module A103

  • 8 galvanic isolated input channels
  • differential voltage, current via shunt connector
    Isolation voltage 100 VDC
  • High accuracy digitalization
  • 24 bit ADU, 100 Hz sample rate per channel with 8 active channels, sum sample rate 800 Hz
  • 2 digital in and 2 outputs
  • input: state, tare, memory reset
    output: state alarm, thresh hold
  • Signal conditioning
  • linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Accuracy class 0.01

  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module A104

  • 8 galvanic isolated input channels
  • thermocouples and voltages in the range of ±80 mV Isolation voltage 100 VDC
  • Cold junction compensation
  • good thermal coupling by means of cold junction compensation per connector
  • Dynamic linearization
  • optimized positioning of the interpolation points within the selected range, type B, E, J, K, L, N, R, S, T, U
  • High accuracy digitalization
  • 24 bit ADU, 100 Hz sample rate per channel with 8 active channels, sum sample rate 800 Hz
  • Signal conditioning
  • digital filter, average, scaling, min/max storage, arithmetic, alarm
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Accuracy class 0,01

  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Modul A106

  • 2 analog input channels
  • Strain gage and inductive measuring bridges
    (full, half, quarter), LVDT, RVDT
  • DC and carrier frequency (CF) principle
  • DC excitation, 600 Hz CF excitation, 4.8 kHz CF excitation for bridges
  • 1 analog output per channel
  • Voltage ±10 V, 10 kHz
  • Fast high accuracy digitalization
  • 24 bit ADU, 10 kHz sample rate per channel
  • 1 digital in or output per channel
  • input: state, tare, memory reset
    output: state alarm, thresh hold
  • Signal conditioning
  • 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • RS485 fieldbus interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module A107

  • 4 universal analog input channels
  • voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges
  • Fast high accuracy digitalization
  • 24 bit ADU, 10 kHz sample rate per channel
  • Signal conditioning
  • 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • RS485 fieldbus interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module A108

  • 8 galvanic isolated input channels
  • differential voltage, current via shunt connector Isolation voltage 100 VDC
  • High accuracy digitalization
  • 24 bit ADU, 10 kHz sample rate per channel with
    8 active channels, sum sample rate 80 kHz
  • 2 digital in and 2 outputs
  • input: state, tare, memory reset
    output: state alarm, thresh hold
  • Signal conditioning
  • linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115,2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Accuracy class 0,01

  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module A109

  • 4 galvanic isolated analog output channels
  • voltage ±10 V, current 4…20 mA selectable Isolation voltage 500 VDC
  • DAC-resolution 16 bit
  • 100 kHz with 1 channel, 10 kHz with 4 channels
  • 4 digital inputs and 4 digital outputs
  • configurable as 2 counter, 2 frequency, or 2 PWM inputs, 2 frequency or PWM output, state in or output
  • Frequency in and outputs
  • frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
  • Counter
  • For/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
  • PWM in and output
  • measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
  • Outputs freely scalable
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus, up to 115.2 kbps: Modbus-RTU, ASCII
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Modul A123

  • 4 galvanically isolated input channels
  • Voltages at high potential, ranges 100 mV, 1 V, 10 V
  • Insulation voltage 1200 VDC
  • short-term 5000 VDC
  • Fast high accuracy digitalization
  • 24 bit ADU, 10 kHz sample rate per channel
  • Signal conditioning
  • 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • RS485 fieldbus interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Modul A124

  • 4 galvanically isolated input channels
  • for non-insulated thermocouples at high potential
  • Insulation voltage 1200 VDC
  • short-term 5000 VDC
  • Cold junction compensation

  • Dynamic linearization
  • Optimum positioning of interpolation points in selected range, types B, E, J, K, L, N, R, S, T, U
  • High accuracy digitalization
  • 24 bit ADU, 10 kHz sample rate per channel with 8 active channels, sum sample rate 80 kHz
  • Signal conditioning
  • digital filter, average, scaling, min/max storage, arithmetic, alarm
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Modul A128

  • 4 galvanically isolated input channels
  • Voltages, ranges 40 V, 120 V, 400 V, 1200 V
  • Insulation voltage 1200 VDC
  • short-term 5000 VDC
  • Fast high accuracy digitalization
  • 24 bit ADU,
    100 kHz sample rate per channel with 2 channels,
    50 kHz sample rate per channel with 4 channels
  • Signal conditioning
  • 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
  • RS485 fieldbus interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module D101

  • 8 digital inputs and 8 digital outputs
  • configurable as counter, frequency, PWM and time inputs, frequency or PWM output, state in or output
  • State in and outputs
  • process- and host controlled
  • Frequency in and outputs
  • frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
  • Counter
  • for/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
  • PWM in and outputs
  • measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
  • Time measurement
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals, power supply and interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module D104

  • 16 digital inputs
  • state, single or bit set, host controlled
  • Configurable threshold
  • TTL or high level (EN61131-2, Type1)
  • Short reaction time
  • 10 µs per input
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller<
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals (2 groups x 8 inputs), to power supply and to interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑
 

Q.bloxx Module D105

  • 16 digital outputs
  • state, single or bit set, host controlled
  • High possible load
  • 30 VDC / 500 mA short circuit proof
  • Short reaction time
  • 10 µs up to 1 ms per input
  • RS485 fieldbus-interface
  • up to 48 Mbps: LocalBus
    up to 115.2 kbps: Modbus-RTU, ASCII
  • Connectable to any Test Controller
  • e.g. Q.gate or Q.pac
  • Galvanic isolation
  • of I/O-signals (2 groups x 8 inputs),
    to power supply and to interface
    Isolation voltage 500 VDC
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC

  • DIN rail mounting (EN 50022)
up to table ↑

 
 
© 2012 Gantner Instruments: Intelligent Solutions for Measurement and Test Automation - Imprint
--
© Gantner Instruments Test & Measurement GmbH, Heidelberger Landstr. 74, 64297 Darmstadt, Phone: +49 6151 95136-0, Fax: +49 6151 95136-26 - The preparation of all the contents and details included on Internet pages is undertaken without accepting liability for the completeness and correctness of this information. - Page: http://www.gantner-instruments.com/distributed-systems/q-series/measure-io, February 4, 2012