Hint: In case you can not see the complete table use the F11 key to switch to full screen mode.
Q.bloxx Module A101
- 2 universal analog input channels
- voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges, IEPE-sensors
- Fast high accuracy digitalization
- 24 bit ADU, 100 kHz sample rate per channel
- 1 digital in or output per channel
- input: state, tare, memory reset
output: state alarm, thresh hold - Signal conditioning
- 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- TEDS
- class 1 and class 2, according IEEE 1541.4
- RS485 fieldbus interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module A102
- 1 analog input channel
- measuring bridge (full, half, quarter), IEPE-sensors, voltage, current
- 1 analog output
- voltage ±10 V and current 0 up to 25 mA selectable, 100 kHz
- Fast high accuracy digitalization
- 19 Bit ADC - SAR (without delay time), 100 kHz sample rate
- 4 digital inputs, 2 digital outputse
- input: state, tare, memory reset
output: state alarm, thresh hold - Signal conditioning
- 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- TEDS
- class 1 and class 2, according IEEE 1541.4
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Additional RS 485 fieldbus interface
- to control an 8-channel multiplexer for multi channel systems, 10 Hz per channel
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module A103
- 8 galvanic isolated input channels
- differential voltage, current via shunt connector
Isolation voltage 100 VDC - High accuracy digitalization
- 24 bit ADU, 100 Hz sample rate per channel with 8 active channels, sum sample rate 800 Hz
- 2 digital in and 2 outputs
- input: state, tare, memory reset
output: state alarm, thresh hold - Signal conditioning
- linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Accuracy class 0.01
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module A104
- 8 galvanic isolated input channels
- thermocouples and voltages in the range of ±80 mV Isolation voltage 100 VDC
- Cold junction compensation
- good thermal coupling by means of cold junction compensation per connector
- Dynamic linearization
- optimized positioning of the interpolation points within the selected range, type B, E, J, K, L, N, R, S, T, U
- High accuracy digitalization
- 24 bit ADU, 100 Hz sample rate per channel with 8 active channels, sum sample rate 800 Hz
- Signal conditioning
- digital filter, average, scaling, min/max storage, arithmetic, alarm
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Accuracy class 0,01
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Modul A106
- 2 analog input channels
- Strain gage and inductive measuring bridges
(full, half, quarter), LVDT, RVDT - DC and carrier frequency (CF) principle
- DC excitation, 600 Hz CF excitation, 4.8 kHz CF excitation for bridges
- 1 analog output per channel
- Voltage ±10 V, 10 kHz
- Fast high accuracy digitalization
- 24 bit ADU, 100 kHz sample rate per channel
- 1 digital in or output per channel
- input: state, tare, memory reset
output: state alarm, thresh hold - Signal conditioning
- 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- RS485 fieldbus interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface Isolation voltage 500 VDC
- Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module A107
- 4 universal analog input channels
- voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges
- Fast high accuracy digitalization
- 24 bit ADU, 10 kHz sample rate per channel
- Signal conditioning
- 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- RS485 fieldbus interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface
- Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module A108
- 8 galvanic isolated input channels
- differential voltage, current via shunt connector Isolation voltage 100 VDC
- High accuracy digitalization
- 24 bit ADU, 10 kHz sample rate per channel with
8 active channels, sum sample rate 80 kHz - 2 digital in and 2 outputs
- input: state, tare, memory reset
output: state alarm, thresh hold - Signal conditioning
- linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus
up to 115,2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Accuracy class 0,01
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module A109
- 4 galvanic isolated analog output channels
- voltage ±10 V, current 4…20 mA selectable Isolation voltage 500 VDC
- DAC-resolution 16 bit
- 100 kHz with 1 channel, 10 kHz with 4 channels
- 4 digital inputs and 4 digital outputs
- configurable as 2 counter, 2 frequency, or 2 PWM inputs, 2 frequency or PWM output, state in or output
- Frequency in and outputs
- frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
- Counter
- For/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
- PWM in and output
- measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
- Outputs freely scalable
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus, up to 115.2 kbps: Modbus-RTU, ASCII
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Modul A123
- 4 galvanically isolated input channels
- Voltages at high potential, ranges 100 mV, 1 V, 10 V
- Insulation voltage 1200 VDC
- short-term 5000 VDC
- Fast high accuracy digitalization
- 24 bit ADU, 10 kHz sample rate per channel
- Signal conditioning
- 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- RS485 fieldbus interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Modul A124
- 4 galvanically isolated input channels
- for non-insulated thermocouples at high potential
- Insulation voltage 1200 VDC
- short-term 5000 VDC
- Cold junction compensation
- Dynamic linearization
- Optimum positioning of interpolation points in selected range, types B, E, J, K, L, N, R, S, T, U
- High accuracy digitalization
- 24 bit ADU, 100 Hz sample rate per channel with 8 active channels, sum sample rate 800 Hz
- Signal conditioning
- digital filter, average, scaling, min/max storage, arithmetic, alarm
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Modul A128
- 4 galvanically isolated input channels
- Voltages, ranges 40 V, 120 V, 400 V, 1200 V
- Insulation voltage 1200 VDC
- short-term 5000 VDC
- Fast high accuracy digitalization
- 24 bit ADU,
100 kHz sample rate per channel with 2 channels,
50 kHz sample rate per channel with 4 channels - Signal conditioning
- 16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
- RS485 fieldbus interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑ Q.bloxx Module D101
- 8 digital inputs and 8 digital outputs
- configurable as counter, frequency, PWM and time inputs, frequency or PWM output, state in or output
- State in and outputs
- process- and host controlled
- Frequency in and outputs
- frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
- Counter
- for/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
- PWM in and outputs
- measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
- Time measurement
- RS485 fieldbus-interface
- up to 48 Mbps: LocalBus
up to 115.2 kbps: Modbus-RTU, ASCII - Connectable to any Test Controller
- e.g. Q.gate or Q.pac
- Galvanic isolation
- of I/O-signals, power supply and interface
Isolation voltage 500 VDC - Electromagnetic Compatibility
- according EN 61000-4 and EN 55011
- Power supply 10…30 VDC
- DIN rail mounting (EN 50022)
up to table ↑